A heat pump is happiest running steadily. The thing that stops it is a system that keeps satisfying itself: zones closing, flow dropping, the unit short-cycling, and efficiency falling away with every start. A buffer tank is the simplest fix for that.
What the buffer actually does
It adds water volume to the circuit. More volume means the system takes longer to reach temperature, which means longer run cycles and fewer starts. It also guarantees a minimum flow rate when zone valves close, which protects the heat pump and keeps defrost cycles working properly.
50 or 100 litres
The 50 litre tank suits a smaller system with modest zoning and reasonable pipe volume already in the circuit.
The 100 litre tank is the choice for a larger property, for heavily zoned underfloor heating, or wherever most of the emitters can close at once. When in doubt, the larger tank costs little more and is far harder to regret than an undersized one.
Where it goes
Plant room space is the practical constraint. Both tanks need insulating properly, because an uninsulated buffer in a cold space quietly throws away the efficiency it was bought to protect. Plan the position alongside the heat pump and the cylinder rather than fitting it wherever is left.
Cloud control
The CZ-TAW1B Smart Cloud adapter connects an Aquarea system to the internet for remote control and monitoring.
The remote control is the obvious benefit. The useful one is monitoring: being able to see flow temperatures and run patterns after commissioning is how a system gets tuned properly rather than left on its factory settings.
Specifying
Tell us the heat pump model, the zoning and the emitter type and we will size the buffer. See our Aquarea heat pump guide or browse air source heat pumps. Call 01283 380031 | sales@pureclima.co.uk.