Duco Sensors and Controls Explained: Box Sensors, Room Sensors and Control Valves

Short answer: Duco splits its controls into three jobs. Box sensors sit inside the DucoBox and measure the extracted air. Room sensors and user controllers go on the wall and give a room its own reading or its own switch. Control valves are extract valves with a sensor built in, used on the DucoBox Focus so each room regulates itself. Which ones you can fit depends on the unit you own, so start there.

Duco CO₂ room sensor with control, RF or wired, white finish

Why demand control matters

A ventilation system running at a fixed rate is either wasting energy or under-ventilating, usually both at different times of day. Demand control measures something that tracks occupancy and moisture — carbon dioxide and relative humidity — and raises or lowers the rate accordingly.

CO₂ is the useful proxy for how many people are in a room and for how long. It is what you want in bedrooms, living rooms and open kitchens. Relative humidity is what matters in bathrooms, utility rooms and laundry areas, where the problem is moisture rather than occupancy. Several Duco sensors combine both.

Box sensors: upgrading the unit itself

Box sensors mount inside the DucoBox and read the air being extracted, giving whole-house demand control from a single component. They are unit-specific:

A box sensor is the cheapest route from fixed-rate to demand-led operation, but it responds to the average of everything being extracted. If you want one room to be able to override the rest, you need a room sensor or a control valve as well.

Room sensors and user controllers

These are the wall-mounted devices, available in white and black and in RF wireless or wired versions.

Device What it does Typical location
User controller, RF/battery Four manual ventilation settings, no sensing, no wiring Hallway or landing, retrofit
User controller, RF/wired Four manual ventilation settings Hallway or kitchen, new build
CO₂ room sensor without control Measures CO₂, no manual override Bedrooms
CO₂ room sensor with control CO₂ sensing plus four manual settings Living rooms, open kitchens
Humidity room sensor with control Humidity sensing plus manual settings Bathrooms, utility rooms
Switch sensor RF/230 VAC Detects a light switch or pull cord and boosts ventilation WCs and bathrooms without a sensor

The CO₂ and humidity room sensors and the user controllers are listed as compatible with DucoBox Silent, Focus and Energy. The switch sensor is the neat answer for a WC where a full sensor is hard to justify: it reuses the existing light switch as a boost trigger.

If you are surface-mounting rather than recessing into a back box, add the surface-mounted box for controllers and sensors.

Control valves: sensing at the extract point

Duco CO₂ control valve 75 m³/h for living rooms and open kitchens, DucoBox Focus

Control valves are the distinctive part of a DucoBox Focus system. Each valve contains its own sensor and damper, so it regulates extract in that room independently. They are selected by room type and flow rate:

Where two rooms share one duct run, the duplicator for control valves lets a single valve position serve both.

Choosing: a quick route

  1. Identify your unit. Reno, Silent, Focus, Energy Comfort, Energy Sky or Energy Premium — this rules most options in or out immediately.
  2. Decide the level of control. Whole-house (box sensor), room-by-room (room sensors), or per-extract-point (control valves on a Focus).
  3. Pick the measurement per room. CO₂ for occupied rooms, humidity for wet rooms, both where a bathroom doubles as a WC.
  4. Choose wired or RF. Wired where cabling is already planned; RF for retrofit and for finished rooms.
  5. Add a manual override where people expect one. A user controller in the hallway covers the household's "just boost it" instinct without undermining the automatic control.

Before you order, confirm

  • Your DucoBox model, checked against the compatibility line on each product page
  • Whether you need the "with control" version of a room sensor, or sensing only
  • RF or wired, and whether a battery version suits the location
  • Colour, where white and black versions are listed separately
  • For control valves: the room type and flow rate, which are part of the product name
  • Whether a surface-mounted box is needed

Frequently asked questions

Can I mix box sensors and room sensors?

They do different jobs — one reads the extracted air at the unit, the other reads a specific room — and systems are often specified with both. Check the compatibility line on each product page against your unit, and ask us if the combination is unusual.

What is the difference between a room sensor "with control" and "without control"?

The "with control" versions add four manual ventilation settings to the sensor, so an occupant can override the automatic rate from that room. "Without control" versions sense only.

Do control valves work on a DucoBox Silent?

The control valves listed above are specified for the DucoBox Focus. For a Silent system, demand control normally comes from a box sensor plus room sensors — see DucoBox Silent & Focus MEV explained.

Which valves do the air actually pass through?

Control valves are extract terminals in their own right. Elsewhere in the house you will need standard air valves — our comparison of the DucoVent range covers the Basic, Comfort, Premium and Design options.

Next step

Browse the full range in the MVHR controllers and sensors collection, or start from the unit: our guide to choosing a DucoBox sets out which controls suit which system. If you want a control schedule put together room by room, send us your room list and we will specify it.