DucoBox Energy Premium 325 vs 400: Zones, Heater and Handing Explained

Short answer: the DucoBox Energy Premium comes in sixteen versions, but they are really four decisions multiplied together: 325 or 400 m³/h, one zone or two, with or without an integrated pre-heater, and left-hand or right-hand. Get those four right and the part number follows automatically. This guide explains what each choice changes.

DucoBox Energy Premium 400-2ZH MVHR unit, two-zone with integrated heater, right-hand orientation

What the Energy Premium is

The Energy Premium is DUCO's flagship mechanical ventilation unit with heat recovery (MVHR): a balanced system that extracts stale air from wet rooms and supplies filtered fresh air to habitable rooms, recovering heat from the outgoing airstream on the way. Every version shares the same core specification:

  • Heat recovery efficiency of 88–89% measured to EU 1253/2014, with an A+ energy label
  • Casing dimensions of 740 × 957 × 585 mm (W × H × D)
  • Five Ø160 mm duct connections (Ø190 mm external)
  • A steel casing with acoustic lining and fan placement chosen to keep noise down
  • Constant-pressure automatic calibration, which DUCO states can save up to 50% of commissioning time

It is aimed at passive houses, low-energy new builds and high-specification renovations — projects where airtightness is good enough for heat recovery to pay back properly.

Decision 1: 325 or 400 m³/h

The 325 version is rated at 325 m³/h (90 l/s) at 150 Pa. The 400 version is rated at 400 m³/h (111 l/s) at 150 Pa. Both share the same casing and the same five Ø160 mm spigots, so the physical installation is identical — you are buying headroom, not a bigger box.

Work from the design airflow your ventilation designer or SAP assessor has calculated for the dwelling, including any boost rate, and pick the unit that delivers it without running near the top of its curve. A unit working hard at the edge of its capacity is noisier and less efficient than a larger one running gently.

Decision 2: one zone or two

A one-zone (1Z) unit treats the dwelling as a single ventilation zone: one supply rate, one extract rate, varied together.

A two-zone (2Z) unit splits the home into a day zone and a night zone and controls them separately, so bedrooms can be ventilated at night while living space is throttled back, and the reverse during the day. In practice this suits households with distinctly different occupancy patterns upstairs and downstairs, and homes where occupants are sensitive to draughts or fan noise in bedrooms. It does require the duct design to separate those zones, so it is a decision for the design stage rather than an afterthought.

If you want zoning on a unit that is not natively two-zone, DUCO lists multi-zone valves and a branch piece for other DucoBox Energy models — check the individual product page for which unit each part suits.

Decision 3: with or without the integrated pre-heater

The suffix S means no pre-heater fitted; H means an integrated frost-protection heater. A pre-heater warms very cold incoming air before it reaches the heat exchanger, which protects the exchanger from freezing in sustained cold weather and keeps the unit in balanced operation rather than cycling its frost strategy.

Whether you need one depends on the climate at the site and the way the system is designed and controlled. If your designer has specified frost protection, order the H version — retrofitting the function later is not as straightforward as ordering it fitted.

Decision 4: left-hand or right-hand

Energy Premium units are built either left-hand (bevelled side on the left) or right-hand (bevelled side on the right). Unlike the Energy Comfort range, where handing is handled in software, this is fixed at the point of order.

Handing determines which side the supply and extract connections fall on, so it follows from where the unit sits in the plant space and where the ducts arrive. Confirm this against the installation drawing before ordering — it is the single most common thing to get wrong on an MVHR order.

The sixteen variants

Model Airflow at 150 Pa Zones Pre-heater Orientation
325-1ZS 325 m³/h (90 l/s) 1 No Left or right
325-1ZH 325 m³/h (90 l/s) 1 Integrated Left or right
325-2ZS 325 m³/h (90 l/s) 2 No Left or right
325-2ZH 325 m³/h (90 l/s) 2 Integrated Left or right
400-1ZS 400 m³/h (111 l/s) 1 No Left or right
400-1ZH 400 m³/h (111 l/s) 1 Integrated Left or right
400-2ZS 400 m³/h (111 l/s) 2 No Left or right
400-2ZH 400 m³/h (111 l/s) 2 Integrated Left or right

Each row exists in both a left-hand and a right-hand build, which is how eight configurations become sixteen stocked part numbers. A few examples:

The full set of sixteen is listed in the MVHR units collection.

Parts to order alongside the unit

Before you order, confirm

  • The design airflow, so 325 or 400 is the right capacity
  • Whether the ventilation design separates day and night zones
  • Whether frost protection has been specified
  • The handing, read from the installation drawing, not assumed
  • That 740 × 957 × 585 mm fits the plant space with service access
  • That the duct design uses Ø160 mm (Ø190 mm external) at the unit

Frequently asked questions

Can I change the handing after delivery?

No. Handing on Energy Premium is a build option, identified as left-hand or right-hand by the bevelled side of the casing, so it has to be correct at the point of order. If handing is likely to change late in the programme, speak to us before placing the order.

Is a two-zone unit worth it in a small house?

It depends on the duct design rather than floor area. Two-zone control only delivers a benefit if the supply ductwork is split into day and night zones; in a system designed as one zone, a 1Z unit does the same job for less.

How does Energy Premium compare with Energy Comfort?

Energy Comfort is a four-spigot platform with software-selectable handing, while Energy Premium uses five Ø160 mm spigots with fixed handing and offers native one- or two-zone versions. Our DucoBox range comparison puts both side by side, and DucoBox Energy Comfort Plus MVHR covers the D350, D450 and D550.

What ducting does it need?

Five Ø160 mm connections at the unit, then whatever the design calls for downstream. DucoFlex ventilation ducting explained covers DUCO's semi-rigid system, plenums, silencers and terminals.

Next step

If you have your four answers, go straight to the MVHR units collection and pick the matching part number. If one of them is still open — most often handing or the pre-heater — send us the details and we will check the configuration against your drawings before you commit.