Skip to content

Free Ventilation estimate  01283 380031 

✌🏼 Next Day Delivery

Cart
Buying Guide

DucoBox Energy Comfort vs Comfort Plus: Which MVHR Unit?

Short answer: the Energy Comfort range covers 325 and 400 m³/h; Comfort Plus extends it to 350, 450 and 550 m³/h and adds automatic calibration. If your design airflow fits within the Comfort range and you are happy to commission by hand, Comfort is the simpler buy. If the dwelling is larger, or you want the unit to balance itself, Comfort Plus is the one.

DucoBox D450 Energy Comfort Plus MVHR unit, 450 m³/h at 200 Pa with automatic calibration

The two ranges side by side

Unit Airflow Duct connections Dimensions (W×H×D) Weight
Energy Comfort D325 325 m³/h (90 l/s) at 150 Pa 4 × Ø160 mm 700 × 705 × 525 mm 21 kg
Energy Comfort D400 400 m³/h (111 l/s) at 200 Pa 4 × Ø180 mm 756 × 800 × 584 mm 31 kg
Comfort Plus D350 350 m³/h (97 l/s) at 200 Pa See product page
Comfort Plus D450 450 m³/h (125 l/s) at 200 Pa See product page
Comfort Plus D550 550 m³/h (153 l/s) at 200 Pa See product page

Read the pressure as well as the flow. The D325 figure is quoted at 150 Pa and the others at 200 Pa, so the headline numbers are not directly comparable — a unit rated at a higher pressure is doing more work for the same cubic metres. Compare against the external static pressure your duct design actually imposes.

What automatic calibration changes

Commissioning an MVHR system means setting every supply and extract flow to its design figure and getting total supply to balance total extract. Done by hand, it is a slow, iterative job with an anemometer: adjust a valve, re-measure, find you have disturbed another branch, start again.

The Comfort Plus units carry automatic calibration, which is what the AUTO in their product names refers to. In practice it shortens commissioning and makes it more repeatable — valuable on larger systems with many branches, where manual balancing takes longest and drifts furthest.

It does not remove the need for a competent commissioning engineer, and it does not rescue a badly designed duct layout. What it does is take the arithmetic out of an otherwise laborious process.

The bypass, on both ranges

Both Energy Comfort units are listed with DUCO's patented double bypass, 100% software controlled, with left or right handing selected in software rather than fixed at the factory.

Software handing is a practical advantage over the Energy Premium, where left-hand and right-hand are separate part numbers chosen at order. If the plant location might move during the build, a software-handed unit removes one way for the order to go wrong.

A summer bypass routes incoming air around the heat exchanger when you do not want heat recovered — a cool night in July, for instance, where the point of ventilation is to remove heat rather than retain it.

Fan power and running cost

The D325 uses two 59 W fans; the D400 uses two 72.5 W. Those are maxima, not continuous draw: a demand-controlled system spends most of its life well below full speed. Fan power nevertheless indicates the unit's capacity to overcome duct resistance, which is another reason to keep duct sizing generous — a smaller unit on well-designed ducting can be quieter and cheaper to run than a bigger one fighting a cramped layout.

Parts shared across the ranges

Several accessories are listed for Energy Comfort and Comfort Plus together, which simplifies specification:

Filters differ by model: the D325 and the D400 / Comfort Plus take different sets, listed in our Duco MVHR filter guide.

Which should you choose?

  • Design flow up to 325 m³/h, straightforward layout — Energy Comfort D325. Smallest and lightest of the group at 21 kg, Ø160 mm connections.
  • Up to 400 m³/h — Energy Comfort D400, remembering it steps up to Ø180 mm connections and 31 kg.
  • 350 m³/h or more, or many branches to balance — Comfort Plus, where automatic calibration starts to pay back.
  • 450–550 m³/h — Comfort Plus D450 or D550; nothing in the Comfort range reaches these rates.
  • Passive house or two-zone control needed natively — look at Energy Premium instead.
  • No cupboard for the unit — the ceiling-mounted Energy Sky D275 may suit better.

Before you order, confirm

  • Design airflow and the pressure it is quoted at
  • Duct connection size — Ø160 mm on the D325, Ø180 mm on the D400
  • Plant space in three dimensions, with filter access
  • Weight and how the unit will be supported: 21 kg and 31 kg are very different lifts
  • Whether frost protection is required, and so whether to add the pre-heater
  • Whether zoning is needed, and therefore multi-zone valves and a branch piece

Frequently asked questions

Is Comfort Plus just a bigger Comfort?

Not only. It extends the range upward to 550 m³/h and adds automatic calibration. The D350 overlaps the Comfort range in capacity, so at that size you are choosing the calibration feature rather than more airflow.

Can I add automatic calibration to an Energy Comfort later?

It is part of the Comfort Plus units rather than an accessory, so this is a decision to make at purchase.

How does this compare with Energy Premium?

Energy Premium offers native one- and two-zone versions, five Ø160 mm spigots and an integrated pre-heater option, with handing fixed at order. See the Energy Premium buying guide, or the whole-range comparison.

What ducting do these units need?

Ø160 mm or Ø180 mm at the unit, then the design's chosen radial duct beyond the manifold. See manifolds, adapters and flow regulators and DucoFlex duct sizes.

Next step

Compare all the units in the MVHR units collection, or read DucoBox Energy Comfort Plus MVHR for a closer look at the D350, D450 and D550. If you have the design airflow and external static pressure, send them to us and we will confirm which unit suits.

Previous Post Next Post

Leave A Comment